Ethernet hybrid module with 8 optocoupler inputs and 8 relay outputs for loads up to 10W
381,59 € Prices plus statutory VAT | plus shipping and handling
Availability:
In stock!
Delivery in 2-3 working days
Technical description – Yamutec® 8-fold Ethernet hybrid module
The 8 channel Ethernet hybrid module has 8 optocouplers at the inputs and 8 relays at the outputs. The galvanic isolation optimally protects the control PC from overvoltages. It is also possible to connect the hybrid module to the network and the Internet via the 100/10 Mbit interface. This allows the states of the relays to be controlled and monitored with our Yamutec I/O Remote app.
The Optocoupler of the hybrid module capture a signal voltage of 3V to 30V AC/DC at a maximum input current of 10mA. The isolation voltage can be up to 2.5KV AC for 1 minute. The reed relays at the outputs work with a maximum switching current of 0.5A and a switching voltage of 30V AC/DC. The supply voltage is 7V to 24V DC via a pluggable screw terminal.
Area of application of the hybrid module from Yamutec
Wherever you want to switch loads without interference and your devices need to be protected from surges or transients, you will find the Yamutec 8-fold Ethernet hybrid modules. The optocouplers realize reliable and very fast acquisition of input signals. You can switch loads safely and cost-effectively using the 8 relays at the output. You also benefit from the timeout protection on the outputs, which switches the relays on or off immediately in the event of a fault.
When developing our hybrid modules, we paid attention to compliance with RoHS and EMC, so all of our modules are perfectly prepared for industrial use. In the robust aluminum housing, the electronics are very well protected from the harsh environment of a production hall and can also be easily mounted on a DIN rail.
8-fold Ethernet hybrid module with 100/10 Mbit Ethernet interface
Our hybrid modules were specifically designed for easy remote maintenance, control and monitoring. The module can be connected to the company network via the fast Ethernet connection and controlled via the Internet. To do this, simply use our included software to assign a port, the IP, a subnet mask and the gateway to the module. You can then control it via our Yamutec I/O Remote app and monitor the status of the outputs. Several 8-fold Ethernet hybrid modules can also be cascaded using the individual MAC address.
Reliable signal acquisition and amplification with our Ethernet hybrid module with 8 inputs and outputs – request an offer now! We also have ETH 16 hybrid modules for load circuits up to 3A on offer!
Technical data
ETHERNET INTERFACE | |
---|---|
supply voltage | External 7V to 24V DC via plug-in screw terminal |
interface | 100/10 Mbit Ethernet (galvanically isolated) IP address can be assigned statically or obtained via DHCP |
control LEDs | Internal 5V supply voltage (green LED) Interface activity (green LED) Timout shutdown (orange LED) I/O activity (blue LED) Error message (red LED) |
EXITS | |
Terminals 1 – 16 | 8 relay outputs, Galvanically isolated via relays Max. switching voltage: 30V AC / 30V DC Max. switching current: 0.5A AC / 0.5A DC Max. transport current: 1.25A AC / 1.25A DC Max. switching power: 10W Switching time: < 1 ms |
Timeout function | Selectable timeout protection when the module is not reachable. e.g. in the event of a software crash (outputs can be individually selected) |
connector | 2 ROW MULTI CONNECTION SYSTEM 100% protection against mismating Can be coded by cutting off the coding lugs |
ENTRANCES | |
Terminal 17 – 32 | 8 optocoupler inputs 3V – 30V AC/DC signal voltage Isolation voltage: 2.5KV AC for 1 minute Maximum input current: 10mA |
connector | 2 ROW MULTI CONNECTION SYSTEM 100% protection against mismating Can be coded by cutting off the coding lugs |
DIMENSION | |
Dimensions Weight |
135mm x 105mm x 74.5mm (L x W x H) 490g |
Downloads
MANUAL | |
---|---|
Instructions | German English |
SOFTWARE | |
---|---|
sample software | VB6, VB.NET , C#, LabView/ without installation |
API | Developer tool (Dynamic link library) |
DATA SHEET | |
---|---|
Outputs 1 – 16 | SIP 1 Form A - 10W molded dry reed relays |